Ambica Boiler is mainly concerned in manufacturing Steam Boilers, Heat Exchangers , Incinerators and Unfired Pressure Vessels ( Gas Storage and Mobile tanks) according to Indian Boiler Regulation 

Ambica Boiler

156/26, Kailashnagar Estate, 

Opp. New Telephone Exchange, 

F. Road, G.I.D.C., Vatva, 

Ahmedabad-382 445. 

Telefax :+91-79-30918007,
        +91-25831134

Mobile : +91-9824343561       
      +91 98203 71031

 

 Oil Fired - Thermic Fluid Heater

 

 
Details Unit

ABT-50

ABT-100

ABT-200

ABT-400

ABT-600

ABT-1000

Heat Output

Kcal/Hr

50.000

1.00.000

2.00.000

4.00.000

6.00.000

10.00.000

Outlet Temperature(max)

oC

300

300

300

300

300

300

L.D.O.
Fuel Consumption
F.O.

Kg/hr

Kg/hr

5.7

-

11.4

-

22.8

-

45.6

47.8

57.0

71.8

102.6

119.6

Thermal Efficiency

%

87

87

87

87

87

87

Thermic Fluid pump Motor

H.P.

2.0

3.0

7.5

10.0

12.5

25.0

Blower Motor

H.P.

1.0

1.0

1.0

2.0

3.0

5.0

Thermic Fluid Pump Rating

Ltr/hr

6.000

12.000

18.000

30.000

36.000

45.000

Fuel Oil Pre-Heater (For F.O.)

K.W.

-

-

-

3

6

9

Burner Control  

ON-OFF

ON-OFF

ON-OFF

ON-OFF

ON-OF

LOW-HIGH

Total Connected Electrical Load

H.P.

3

4

8.5

12

15.5

30

Expansion Tank Capa.

Liters

150

150

150

200

400

400

Electric supply – 415 Volts + 5% 50 H2 3ph – 6Wire.

  

LDO Gross Calorific Value : 10700Kcal/Kg.
LDO Net Calorific Value : 10200Kcal/Kg.
FO Gross Calorific Value : 10200Kcal/Kg.
FO Net Calorific Value : 9650Kcal/Kg.

 

Home  |  Product  |  Profile  |  Contact  |  Resource

 